118

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 2

Installation Instructions

Modules are installed by pressing them onto the 1715-A3IO three-slot base unit.

Follow these steps.

1. Inspect the connector pins, referring to

page 107

.

2. Inspect the identification labels on the sides of the modules and record the

location and the module information shown on the label.

This helps you when installing a new or replacement module in the future

by allowing you to order the replacement parts without disturbing the

system.

3. Check the coding pegs on the termination assembly and verify they match

the sockets on the back of the I/O module, referring to

page 108

.

4. Verify that the slot on the head of the module clamp screw is vertical,

referring to

page 108

.

5. Place the new module on to the dowel pin on the I/O base unit, referring

to

page 109

.

6. Push the module in until the connectors are fully mated.

32069-M