Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 5

Configure the Redundant I/O System

The Fault/Program Action tab appears.

12. Click OK.

Table 34 - Fault/Program Action Parameters

Parameters

Description

Point

Click the point number to configure parameters for the specified point (0…7).

Output State During

This value

Indicates the following controller tag settings

Program mode

On

Off

Hold

ProgMode = 0
ProgValue = 1

ProgMode = 0
ProgValue = 0

ProgMode = 1
ProgValue = The value previously set.

Fault mode

On

Off

Hold

FaultMode = 0
FaultValue = 1

FaultMode = 0
FaultValue = 0

FaultMode = 1
FaultValue = The value previously set.

Communication Failure If Communication Fail in Program Mode

Specify the action to take when communication fail in Program mode. Choose one of the following:

Leave outputs in Program mode state – When selected, lets you maintain outputs in the Program

mode state (default). When cleared, changes outputs to the Fault mode state.

Leave outputs in Program mode state appears dimmed only when in Hard Run mode.

Change outputs to Fault mode state – When selected, lets you change outputs to the Fault mode

state. When cleared, changes outputs to the Program mode state.

Change outputs to Fault mode state appears dimmed only when in Hard Run mode.