Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

159

Configure the Redundant I/O System

Chapter 5

Add the 1715-AENTR Adapter

to the I/O Configuration Tree

Once the project, controller and Ethernet module are configured, you are
ready to add the 1715 adapter. In this section, you do the following:

Add the 1715-AENTR adapter module to the project.
Configure the adapter for the EtherNet/IP Network.

Step 1: Configure the Adapter for the EtherNet/IP Network

Plan IP addresses by doing the following.:

You need to use two IP addresses.
You need to know the subnet mask for the Ethernet network the

redundant modules are to operate on.

Options for Setting the IP Addresses of 1715-AENTR Modules

You can set the IP address of the redundant AENTR modules in the adapter base

by using the following:

A BOOTP/DHCP utility. A BOOTP/DHCP utility is provided with

the Logix Designer application out of the box. See

Step 1: Assign an IP

Address on the BOOTP/DHCP Server on page 111

.

Module Configuration properties specified in RSLinx Classic software, if

the modules are already configured.

Module Properties dialog box accessed by using RSLogix 5000

programming software or the Logix Designer application, if the modules

are already configured.

If you are configuring your redundant EtherNet/IP modules by using any

of the software options listed above, see the EtherNet/IP Modules in

Logix5000 Control Systems User Manual, publication

ENET-UM001

for

more information.

Ethernet Network

We recommend that static IP addresses be assigned to EtherNet/IP modules in

Logix5000 control systems.

We recommend that you not use dynamic IP addresses because if a power outage

or other network failure occurs, modules with dynamic IP addresses can be

assigned new addresses when the failure is resolved. If the IP addresses of modules

change, you could experience a loss of control or other serious complications with

your system.

However, if you must use the DHCP feature, you can use the Stratix 8000™

switch, which can be configured to provide the same IP address to any given port.

See Logix5000 Control Systems User Manual, publication

ENET-UM001,

for

more information.