Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 162

Advertising
background image

162

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 5

Configure the Redundant I/O System

4. Click Change.

The Module Definition dialog box appears.

5. Click OK.

Table 24 - Module Definition Parameters

Parameters

Description

Series

Module series letter.

Revision

Major: Choose the revision of the module.
Minor: Set the module’s minor revision. This field is enabled while offline, and while in the Program, Remote

Program, and Remote Run modes. It appears dimmed when in Run mode, or when electronic keying is set to

Disable Keying.
For SIL 2 applications, choose version 2.01.07 or later for 1715-AENTR modules.

Electronic Keying

Electronic Keying, see

Appendix B.

Valid values are Compatible Module (default), Exact Match, or Disable Keying.

Connection

Leave as ‘Data’ - Listen Only is not supported.

Redundant

Always Yes.

SIL 2 Safety

Choose No if SIL 2 operation is not required.
Choose Yes to enable SIL 2 operation. The safety pull-down menu appears only if using Add-on Profile version

2.01.007 or later. Two new tabs are available for SIL 2 configuration if you choose Yes. For information on SIL 2

configuration, see

Chapter 6

.

Chassis Size

Choose the chassis size you want to use: 5,8,11,14,17,20,23,26.
The chassis size is a function of the number of bases installed in your system, which come in either groups of three

slots per base for I/O bases; and two slots per base for the redundant adapter base.
All slots in the chassis do not have to be populated.
To extend the size of a chassis, its size must be consistent with the number of base slots used. The minimum

chassis size is 5 slots, built from one 2-slot adapter base and one 3-slot I/O base.