Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 6

1715 Redundant I/O System in SIL 2 Safety Applications

This handles all fault scenarios:

If a controller fault, such as a watchdog fault occurs, the controller goes to

program mode, which causes the 1715 I/O to go to the Program Mode

states.

If there is a system fault that causes a communications loss to the I/O

modules, then the 1715 I/O will go to the Fault Mode states.

If there is a CRTL (Connection Reaction Time Limit) timeout in the

1715-AENTR adapter, then the 1715 output modules will go to the Fault

Mode states.

For the 1715-OB8DE, the configuration is found under the Fault/Program

Action tab.

For the 1715-OF8I, the configuration is found under the Fault/Program Action

tab.

Additional Resources

For more information on using 1715 I/O modules in SIL 2 applications, see the

following resources:

Chapter 7, Using SIL 2 Add-On Instructions with 1715 Redundant I/O

Modules on page 223

Appendix E, PFD and PFH Calculations for a SIL 2 System on page 289

Appendix F, SIL 2 Applications Checklist on page 303

ControlLogix Controllers in SIL 2 Applications, publication

1756-RM001