Enable Change of State

The Point column (on the left side of the Configuration tab) lets you determine

whether a change of state occurs when a field device becomes Off to On or On to

Off.

1. On the Module Properties dialog box, click the Configuration tab.

2. Do one of the following:

Check a checkbox to enable COS for a specific point for either Off to

On or On to Off.

Clear the checkbox to disable the COS for a specific point.

3. Click OK.

See

Threshold Values for Digital Inputs on page 261

for setting custom threshold

configurations.

Field-side Diagnostics

If using the 1715-IB16D thresholds, the user is responsible for designing a circuit

that provides unique voltage levels for Wire OFF, OFF, ON and shorted to 24V

DC. This typically involves an inline and shunt resistor. Typical values for the

inline resistor are 3.9 k. A typical value for the shunt resistor is 15 k. This

generates an OFF voltage of 5V DC and an ON voltage of 14V DC if the supply

voltage is 24V DC.

The digital input module has the ability to detect the voltage level, much like an

analog input module. There are no circuit tests on field wiring. The user defines

their diagnostic granularity by using custom thresholds built in to the channel

configuration. For full diagnostics, the user designs a circuit for which the OFF

state is, for example, 5V DC, and the ON state, which is, for example, 15V DC.

Wire OFF creates 0V DC, which falls below the OFF threshold, and OpenWire

fault status is set HI. A short to 24V DC is above the ON threshold, and Short

Circuit fault status is sent HI.