284

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Appendix C

1715-IB16D Digital Input Module Diagnostics

maintained, it is to recommended a calibration drift check be performed every

two years for most applications.

Although the purpose of checking the calibration of analog modules is the same

for input and output modules, to verify that the module’s accuracy and

repeatability is maintained, the procedures involved differ per module.

When you check the calibration of input modules, you use current, voltage or

ohms calibrators to send a signal to the module and check the correct values are

reported.

When you calibrate output modules, you use a digital multimeter (DMM) to

measure the signal the module is sending out.

Control can be impaired by the calibration drift process.

When you begin the calibration check process, if a real-time connection is

currently open, the module points you are calibrating can fault. We recommend

that you change your controller to Program mode before beginning calibration.

The two general functions in the calibration check process are as follows:

Attaching/generating a Low Reference Signal
Attaching/generating a High Reference Signal

Verify that the physical values correspond to the module read/produced values

within desired tolerances. If not, consider replacement of the affected module.

IMPORTANT

Before beginning calibration checking, do the following:
Stop the process your output module is controlling or your input module is

tracking.

Disconnect input signals and connect test signals. Any control that depends

on the normal input signals will not have them during the calibration check

process.

Disconnect output signals and connect a suitable measuring instrument.

Any control that depends on the outputs from this module will not have

them during the calibration check process.

Make sure the equipment , a Multimeter, is calibrated.

IMPORTANT

The 1715-IF16 and 1715-OF8 modules can be operated with multiple ranges.
Verify that the appropriate Output Range or Input Range is selected before
continuing with the calibration check procedure.