Installation Instructions

Chapter 2

Field Wiring of Analog Input Termination Assemblies

The termination assembly routes each analog input through a circuit similar to

that shown in

Figure 48

. The input channel is protected with a 50 mA fuse.

When an extreme over voltage is applied to the input, the fuse blows. Each analog

input channel is terminated by a precision120

resistor and fed to the module’s

input circuits. The fuses have a plastic fuse cover that must be kept in the closed

position during normal operation. Standard field wiring connections are made at

the terminal blocks on the termination assembly.

With a simplex termination assembly the input signals are routed to one input

module. In duplex configurations they are routed in parallel to two modules.

Figure 48 - Analog Input Termination Assembly Input Circuit

IMPORTANT

These resistors must be considered as part of the field loop circuit. Each channel
has a 50 mA

fuse to prevent component damage in over-current situations.

Input

Circuit

Input

Circuit

Ch. 0…15

+ve

F1 50 mA

100R

2.5V

500mV

0V

20R

-ve

Analog Input Module

Termination Assembly

32111-M