C - 1715-ib16d digital input module diagnostics, Threshold values for digital inputs, Threshold values for digital – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 271: Appendix

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

271

Appendix

C

1715-IB16D Digital Input Module Diagnostics

Threshold Values for Digital

Inputs

This section describes how to calculate and set threshold values for digital inputs.

The module determines the channel state and the line fault status by comparing

the channel input voltage with defined threshold values. Line faults, such as short

circuit and wire off, can be determined by using different input voltage values.

With this module, the user can define custom threshold values or use a set of

preset default values. The types of threshold values you choose initially for the

module become inherent in each channel; you can define different thresholds for

individual channels later.

The threshold values determine which end-of-line (EOL) resistor value you

choose, and vice versa, depending on whether you choose the threshold values

first, or the EOL resistor values first.

Advertising