Specify an enclosure, System software – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 54

Advertising
background image

54

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 2

Installation Instructions

Specify an Enclosure

An enclosure for the 1715 Redundant I/O System must be designed for the

specific environmental conditions that are present. It needs to support the weight

of the system, provide mechanical protection and remove the heat that the system

creates. If the application of the adapter module is not using existing power

sources, the power supply units can be placed inside the enclosure.

System Software

Install this software for your 1715 Redundant I/O System:

RSLogix 5000 programming software, version 19 or later, or Studio 5000

environment, version 21 or later

RSLinx Classic software, version 2.57
Microsoft Windows XP Service Pack 2, or higher; Microsoft Windows

Vista; Microsoft Windows 7, 32- and 64-bit; and

Microsoft Windows

2003 Server

ControlFLASH revision 2.001
Adapter Add-on Profile at:

Product Compatibility and Download Center

website

I/O Modules Add-on Profile

Product Compatibility and Download Center

website

ATTENTION: The modules contain static-sensitive devices that can be

damaged by incorrect handling. Label the exterior surface of the enclosure
to caution personnel to observe anti-static precautions when handling the
modules.

IMPORTANT

The adapter ships with factory boot firmware and must be updated before use.
The I/O modules are flashed with the correct firmware.

IMPORTANT

You must ensure that there are no active connections to the 1715 chassis
before performing a firmware update.
After upgrading a revision 1.005 1715 chassis to revision 2.001 or later, power
to the 1715 chassis must be cycled.