Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

201

Chapter

6

1715 Redundant I/O System in SIL 2 Safety

Applications

This chapter provides information on using 1715 I/O modules in a low demand

SIL CL (claim limit) 2 system, such as a ControlLogix-based SIL 2 system. For

SIL 2 safety application requirements specific to installing, programming, and

operating a ControlLogix application, refer to the Using ControlLogix in SIL 2

Applications Safety Reference Manual, publication

1756-RM001

.

Topic

Page

SIL 2 Safety Application Requirements

202

1715 I/O Modules in SIL 2 Safety Applications

202

Typical Configurations

204

Requirements for Using 1715 I/O Modules

207

Using the 1715 Adapter in SIL 2 Applications

208

Using 1715 I/O Modules in SIL 2 Applications

209

Considerations for Sensor and Actuator Configurations

213

Configure SIL 2 Operation

213

Check SIL 2 Reset Status

218

View Module Information

218

Additional Resources

222

IMPORTANT

The TÜV Rheinland Group has approved the 1715 Redundant I/O System for use
in safety-related applications up to and including SIL 2 according to these

standards:
IEC 61508, edition 1, 2000
IEC 61511
Approval requirements are based on the standards current at the time of

certification. See

Appendix E

, PFD and PFH Calculations for a SIL 2 System.

ATTENTION: Personnel responsible for the application of safety-related
programmable electronic systems (PES) shall be aware of the safety

requirements in the application of the system and shall be trained in using the
system.