Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

217

1715 Redundant I/O System in SIL 2 Safety Applications

Chapter 6

Set Safe State Values for Inputs

You must define the safe state values for inputs if the SIL 2 data verification

checks have determined that the connection is not valid and the Connection

Reaction Time Limit (CRTL) has expired.

The default safe state value for digital inputs is OFF; for analog input modules,

the safe state value is 0. Follow these steps to change the default values.

1. Click the Input States When CRTL Expires tab.
2. Use the pull-down menus to choose values for each input point.
3. Click OK.