Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 254

Advertising
background image

254

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Appendix A

Status Indicators

Rack Status

Steady off

No power, unlocked - The module has no power or it is not

locked (via the locking screw).

Steady green

Rack operational - All modules in the rack are operating

without fault.

Steady red

Fault - At least one module in the rack has detected a

fault. Examine the other modules in the rack for their

status indicator condition.

Flashing green/red

Self-test - The module is performing its power-on self

tests.

Flashing amber

Unlocked - Adapter is unlocked from a previously locked

state.

Unlabeled Status 1

Located directly below Rack Status-used in Recovery

mode

Steady off

No power - The module has no power or is not in recovery

mode.

Steady amber

Recovery mode - The module is in Recovery mode.

Flashing amber

Unlocked - Adapter is unlocked from a previously locked

state.

Unlabeled Status 2

Located directly below Unlabeled Status 1-used in

Recovery mode

Steady off

No power - The module has no power or is not in recovery

mode.

Steady amber

Recovery mode - The module is in Recovery mode.

Flashing amber

Unlocked - Adapter is unlocked from a previously locked

state.

Ethernet 1 and 2

Steady off

No power, no link - There is no power or an Ethernet link is

not established.

Steady green

Link present - A valid Ethernet link has been established.

Amber

Activity - Tx and/or Rx activity is present.

Table 54 Adapter Status Indicators

Indicator

State

Description

Advertising