Installation Instructions

Chapter 2

Power Requirements

A 24V DC power supplied is required. See

Install the Power Supply on page 63

for complete details.

Cooling Requirements

The 1715-AENTR adapter module is designed to operate in its specified

environment without forced air cooling. Forced air cooling can be needed in

individual circumstances, such as when the system shares its enclosure with other

heat producing equipment.

Adequate ventilation must be provided for the system and the ambient

temperature in the enclosure must not be higher than the maximum operating

value of 60 °C (140 °F).

The adapter module dissipates all of the power it uses as heat. This is the power

supplied to the terminals on the 1715-A2A adapter base unit. The I/O modules

dissipate some of the power they take from the field power source as heat. The

actual amount of heat depends on the number of channels in use.

The 1715-AENTR adapter module is open-type equipment that is rated IP20.

This provides protection against solid objects over 12 mm (0.47 in.), but does not

provide protection against liquids.

Heating Requirements

If enclosure is in colder environments, temperatures must be kept at

-20 °C (-4 °F) or above.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connections
to this equipment must be powered from a source compliant with the
following:

S

afety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV)

IMPORTANT

Cooling by Convection: For correct cooling of the equipment, fit the base units

in the vertical plane and orientate so the modules are upright, with their
ventilation slots at the top and bottom.