Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 50

Advertising
background image

50

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 2

Installation Instructions

Analog Output Termination Assemblies

Analog output termination assemblies support these features:

Eight output channels for a simplex/duplex configuration
Industry-standard field device connections at the terminal blocks
Analog output channels provide 4…20 mA DC for external field devices
Duplex termination assembly provides increased fault tolerance for output

channels

There are two types of analog output termination assemblies:

A 1715-TASOF8, 8-channel simplex TA that provides termination for 8

single-ended analog output channels and mates with a single 1715-OF8I 8

-channel analog output module

A 1715-TADOF8, 8-channel duplex termination assembly provides fault

tolerant operation for 8 analog output channels through inter-module

communication and by routing the output source current from two

modules to the same field device

IMPORTANT

The dual termination assembly does this by supporting inter-module
communication for current sync operation and by routing the channel outputs
from two 8-channel analog output modules in parallel to 8 field device.

Therefore, each field device receives a current source from a channel on each of
two modules. So if one module fails, or one or more channels fail on a module,
the outputs from the second module continues to supply the field devices.

Advertising