When an analog input module is configured as dual, the analog field loop

connected to channel 0 is automatically fed to both modules. The system

automatically votes the data from the input modules so that you have only one

value presented to the application. The application program is presented with

channel 0 and channel 1 values in a fault tolerant manner so that if either input

module is lost, both values are still available to the application program.

Figure 49 - 1715-TASIF16 and 1715-TADIF16 Analog Input Termination Assemblies

Analog Input Module Field Devices

If there are two field devices, you normally connect them to two channels of a

fault tolerant pair of modules, for example to channel 0 and to channel 1.

The two input values (0 and 1) then need to be voted by using logic or a function

block in the application program. This is accomplished by taking either the

lowest or highest value, depending on the application. The other option is to use

the two values in two simplex input modules, for example, both using channel 0.

In this case, the values still need to be voted in the application program in the

same way as previously stated, but the system has less fault tolerance, as the loss of

one module removes one of the inputs.

32120 M

Fuse

Fuse
Holder

Channel -

Channel +

TB1

TB2

CH0 CH1 CH2 CH3 CH4CH5 CH6 CH7 CH8CH9 CH10CH11CH12CH13CH14CH15

FS1

FS3

FS5

FS7

FS2

J1

16

c

c

c

c

1

1

1

1

16

16

16

J2

J4

J3

FS4

FS6

FS8

FS9

FS11

FS13

FS15

FS10

FS12

FS14

FS16

FH1

FH2

FH7

FH6

FH5

FH4

FH3

FH9

FH8

FH10

FH16

FH15

FH14

FH13

FH12

FH11

FH1

F1

OV OV CH0 CH1 CH2 CH3

CH4 CH5 CH6 CH7 CH8 CH9

CH10 CH11 CH12 CH13 CH14 CH15

TB1

TB2

J1

J2

16

16

1

1

1715-TADIF16

Analog Input Duplex

Termination Assembly

1715-TASIF16

Analog Input Simplex

Termination Assembly

45238

32120-M

Terminal Block Cable This Side

Field Connections This Side

Fuse Cover

Fuse Covers

Polarizing

Pins

Polarizing

Pins

Advertising