Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

307

I/O Tag Definitions

Appendix G

1715-IB16D

CIPConnections

DINT

Total number of active CIP connections

CIPLostPackets

DINT

Total of all CIP packets

TCP Connections

DINT

Total of all TCP connections

CUPUtilization

DINT

Echo of Connection Manager object CPU_Utilization attribute

Table 76 - Input

Tag Name

Data Type

Definition

Table 77 - 16-channel Digital Input, Simplex

Tag Name

Data Type

Definition

Fault

DINT, Binary

Module fault bit:

0 when a module is present and reporting valid data, OxFFF_FFFF when no module is

present, no Logix connection exists, or reported data is valid

Data

INT

Input state, one bit per channel for channels 0…15:

0 = Off/de-energized

1 = On, energized

Status

DINT, bit-field

Redundancy and power status:
Bit Name

Description

8 GroupFault

0 = Good

1 = Any channel or module faulted/failed

PtFault

INT

Channel fault status; one bit per channel for channels 0…15:

0 = Normal

1 = Channel is faulted/failed

Open Wire

INT

Open wire diagnostic status; one bit per channel for channels 0…15:

0 = Normal

1 = Indicates open wire detected

ShortCircuit

INT

Short circuit diagnostic status; one bit per channel for channels 0 …15:

0 = Normal

1 = Indicates short circuit detected

Indeterminate

INT

Indeterminate diagnostic status; one channel per channel for channels 0…15:

0 = Normal

1 = Indicates indeterminate input voltage detected