Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules

If you are using COS, the worst case reaction time from input screw terminal to

output screw terminal is equal to 270 ms plus the following:

Output RPI
Add-On Instruction Module RPI/2
SIL 2 Task Period x 6
SIL 2 Task Watchdog x 2

Using the Add-On Instruction

Data Tags in an Application

Program

The following illustrations provide basic examples of how the

Requested_Output_Data tag and the Reconciled_Input_Data tag could be used

in program logic. Data is written to the requested output and read from the

reconciled input, while the raw data in the module-defined input and output tags

is ignored.

Figure 68 - Requested_Output_Data in Ladder Logic Example

Figure 69 - Reconciled_Input_Data in Ladder Logic Example