Reconfigure a Module Online

The Module Properties dialog box appears.

2. Reconfigure the I/O module.
3. Click OK.

Reconfigure a Module via Ladder Logic

It is sometimes advantageous to change the functional operation of a module in

the ControlLogix system automatically via the user program instead of by using

the Logix Designer application to reconfigure it. This way, changes in the process

can dictate when the reconfiguration takes place rather than you performing that

function manually.

The1715 modules support sending a MSG instruction of type Module

Reconfigure. This MSG instruction can be sent to a module to reconfigure it

without stopping the module.

Use a MSG instruction of type Module Reconfigure to send new configuration

information to an I/O module. During the reconfiguration, the following occurs:

Input modules continue to send input data to the controller.
Output modules continue to control their output devices.

The following steps are used in this example when reconfiguring a module via

ladder logic.

1. Move new configuration parameters to the Configuration portion of the

tag structure associated with the module.

2. Use a message instruction to send a Reconfigure Module service to the

same module.