1715-OB8DE Digital Output Module Functional Block Diagram

Figure 37 - 1715-OB8DE Functional Bock Diagram

Refer to

Figure 37

. The field output channel is controlled by two independent

output switch control units. The field output circuitry is galvanically isolated

from the processor input commands and response lines by an isolated interface

circuit. This architecture protects the system processors from faults in the

module’s output control circuits and possible field device faults.

Module power is produced by the internal isolated power supply, supplied by the

dual redundant system power inputs. Over- and under-voltage protection is

applied to the module internal power supply outputs.

VFIELD 1

VFIELD 2

Response Bus

24V
FIELD
POWER

Response

Command A,B,C

I/0 Command Bus

I/0 Backplane

VFIELD
OV RTN

Power
Combiner

Isolated
Backplane
Interface

PWR Power

Valid

PWR Power

Valid

Response

Command

Command

Dual
Redundant
System
Power

SYS_24V1

SYS_24V2

SYS_OV

Isolated
Power
Supply

Over/Under
Voltage
Protection

PWR

Power
Valid

LED Array

Front Panel

Channel
Status

Module
Status

VREF

Termination
Assembly

CH0

CH7

Transient
Suppression

VMON B

VMON A

Output Control

Output Control

Reverse Voltage
Blocking

IMON B

IMON A

VREF

Data Management
& Output Switch
Control A

PWR Feed Combiner Drives

SPI
Flash

Response

Combined Power Feed

Termination
Assembly

Data Management
& Output Switch
Control B

32107-M1