Add-on instructions, Connection reaction time limit, Using the 1715 adapter in sil 2 applications – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 208

Advertising
background image

208

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 6

1715 Redundant I/O System in SIL 2 Safety Applications

Requirements for

ControlLogix-based SIL 2

Applications

Add-On Instructions

The Add-On Instructions provide a mechanism to verify the validity of data

transferred between the ControlLogix controller and the 1715 adapter. When

you use the Add-On Instructions, the sender of the data adds check data to the

produced data. The receiver of the data uses the check data to verify the integrity

of the consumed data.

Connection Reaction Time Limit

The Connection Reaction Time Limit (CRTL) setting defines the maximum

time that the connection can operate with old data, before substituting the

configured safe state values. If the CRTL expires, the receiver requires a SIL 2

Reset before valid data is provided again.

For an input module, if the CRTL expires before the Add-On Instruction detects

valid data, the value of the affected input assembly transitions to the configured

safe state value. A SIL 2 reset is required before inputs transition from the safe

state to field values.

For an output module, if the CRTL expires before the 1715 firmware detects that

valid output data is received from the Logix controller the output data transitions

to the configured safe state values. In this case, a SIL 2 Reset is required before

outputs can be re-energized.

Using the 1715 Adapter in

SIL 2 Applications

The 1715-AENTR adapter performs the following functions:

External communication with the controller via an Ethernet network
Communication with I/O modules, such as receiving input values, sending

output values, and coordinating diagnostics

Enforcement of the output CRTL on data received from a ControlLogix

controller

For high availability, use two 1715-AENTR adapters in simplex and duplex SIL 2

applications.

IMPORTANT

SIL 1 applications must use the wiring and measures defined for SIL 2
applications. Energize-to-action requires line monitoring for any SIL

application.

IMPORTANT

To meet SIL 2 application requirements in a ControlLogix system, you must use
the 1715 Add-On Instructions described in

Chapter 7

.