Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

91

Installation Instructions

Chapter 2

Figure 39 - Connections to 1715-TASOB8DE and 1715-TADOB8DE Digital Output Termination

Assembly 8-channel Simplex/Duplex

Apply a minimum tightening torque of 0.5 N•m (0.37 lb•ft) to the terminal

screws.

The 24V DC field voltages VFIELD 1 and VFIELD 2, used by the output

module for the output field voltages, are connected at the terminal blocks and fed

via two replaceable 10 A fuses, F1 and F2. These fuses give protection for the

output module against field faults. Field OV (VFIELD RTN) is also routed from

the output module connectors to the terminal block.

Figure 40 - 1715-TASOB8DE Digital Output Simplex Termination Assembly Connections

OV

OV

OV

V1 +

+

V2

V1 +

V2 +

OV

To
Next
TA
(if fitted)

TB1

TB2

TB3

TB4

CH0

CH2

CH4

CH6

CH1

CH3

CH5

CH7

32105-M DO TA Field Wiring

VFIELD1+24V DC

VFIELD2+24V DC

VFIELD RTN OV

DO CH0
DO CH1
DO CH2
DO CH3

DO CH4
DO CH5
DO CH6
DO CH7

F2

F1

Digital Output Module
Fail Safe Channel
Array

32103-M DO Simplex Output

Connections