Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 95

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

95

Installation Instructions

Chapter 2

The module also monitors the input data paths and can detect faults within each

input channel. A visual indication of the module status and individual channel

status is provided by an array of front panel indicators and can be connected to

tags within the Logix Designer application.

The termination assemblies can accept one or two input modules. Each

termination assembly provides passive signal load termination and over-voltage

protection for each input channel. The system provides flexible input

connectivity by mating specific termination assemblies with the relevant number

of input modules.

Field Loop Circuits for Analog Inputs

These circuits can be used for simplex and duplex configurations of analog input

modules. Fit a fuse in each circuit to protect the field wiring.

This field loop connection method is used for two-wire field devices.

Figure 45 - Two-wire Analog Input Field Loop Circuit

IMPORTANT

If a fault occurs during normal operation in a duplex configured system, a
faulted input module can be removed and replaced without disrupting the

input signals to a live system.
Use extreme caution when removing and inserting I/O modules under power
because bending or damaging the pins can fault the system.

Shield

Required

Terminal

Blocks

OV

Termination

Assembly

+24V DC

4…20 mA

2-Wire Analog Input

50 mA

120Ω

32116-M