Chapter 7

Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules

Table 41 - SIL 2 Add-On Instructions

An additional Add-On Instruction called CRC_calculator is automatically

imported when any of the nine Add-On Instructions listed above are imported.

The CRC_calculator instruction calculates the CRC for incoming packets and

compares the result against the actual CRC received in the packet. The

instruction also calculates the CRC that is placed in the outgoing packet.

SIL 2 check data is added to data packets by the producer and this check data is

verified by the consumer to determine the validity of the data transfer.

For input data from the 1715 modules, the 1715-AENTR adapter is the

producer and the ControlLogix controller is the consumer. The 1715-AENTR

adapter adds the check data, and the Add-On Instructions verify that valid data is

received within the module's connection reaction time limit (CRTL). If valid

data is not received within the CRTL, the instruction substitutes the module's

configured safe state values in place of the invalid data.

For output data to the 1715 modules, the ControlLogix controller is the

producer and the 1715-AENTR adapter is the consumer. The Add-On

Instructions add SIL 2 diagnostic information (check data) to the module

assemblies, including a sequence number, source and destination IDs, and CRC.

The 1715-AENTR adapter verifies that valid data is received within the CRTL.

Outputs are placed into the safe state if the CRTL expires.

The 1715 input modules send data only in one direction, from the

1715-AENTR adapter to the ControlLogix controller. In contrast, for the 1715

output modules, data is sent in both directions (status to the controller and

output data from the controller).

The Add-On Instructions perform error rate monitoring on the input data they

process to verify that the maximum allowed error rate for SIL 2 has not been

exceeded. The error rate monitoring is performed automatically, requires no user

configuration, and will shutdown a link (force Add-On Instruction outputs to

shutdown states and require a SIL 2 Reset) immediately when it is detected.

The Add-On Instructions provide an output (CRC_error) that indicates if this

condition has occured.

Module

System Configuration

Add-On Instruction Name

1715-IB16D

Simplex

IB16D_Simplex_SIL2

Duplex

IB16D_Duplex_SIL2

1715-OB8DE

Simplex

OB8DE_Simplex_SIL2

Duplex

OB8DE_Duplex_SIL2

1715-IF16

Simplex

IF16_Simplex_SIL2

Duplex

IF16_Duplex_SIL2

1715-OF8I

Simplex

OF8I_Simplex_SIL2

Duplex

OF8I_Duplex_SIL2

1715-AENTR

Duplex

AENTR_SIL2