Command packets are received from the processor module via the EtherNet/IP

network. The output switch control units decode and vote the output data

addressed to them and set the output FET switches accordingly. The output

voltages are produced from the 24V DC field power input voltages by a power

combiner circuit. Each output channel has a pair of FET switches arranged in a

series that are independently controlled. Load current and voltage monitoring is

provided for each switch. Output channel protection ensures the output circuit is

switched off when the channel load current exceeds a safe limit.

A reverse voltage protection circuit ensures that externally applied voltages to any

output channel do not generate current flow backwards into the module outputs.

In Duplex redundant mode, the two fail-safe output switches per channel are

combined in a parallel arrangement so that they automatically form a fault-

tolerant output configuration. In this configuration, removal and of an output

module is possible without any disruption to a live system.

The module has a range of self-checking functionality. Short circuit and open

circuit line monitoring is provided on all outputs. In addition, each output

channel is tested and checked for ‘stuck-on’ and ‘stuck-off ’ conditions on the

output switch pairs.