Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 8

Redundant I/O System Diagnostics

Table 51 - 1715-OB8DE Module Diagnostic Features

Feature

Description

Redundancy level

Simplex or duplex.

Redundancy status

The status of each module of a duplex pair is available in the input tag.

Change-of-state transport

The connection trigger for the discrete output is change-of-state. Data is produced when output

data is consumed, or when diagnostic data changes state, or at the Requested Packet Interval.

Unlike the discrete input module, change-of-state production cannot be disabled for the discrete

output module.

No load detection

A fault is indicated when no load is detected while the output point is in the off state. No load

detection can be disabled to prevent alarms from appearing for unused points.

Short circuit detection

A fault is indicated when a short circuit/over current condition is detected. The fault indication is

reset when the following occurs.

1. Point is commanded off.

2. A short reset service is sent to the module.

3. A reset is done through a bit in the output tag.

Diagnostic latch

When latching is enabled, diagnostic alarms are latched until they are reset. This aids in detecting

intermittent issues. For output modules, latch reset can occur either through messaging or through

a member of the output tag.

Fault mode

When a connection from a controller exists, and the connection is interrupted, the module outputs

take on a user-selected state. This Fault mode is either Off, On or Hold Last State.

Program mode

When a connection from a controller exists, and the controller is not in Run mode, the module

outputs take on a user-selected state. This Program (a.k.a. ‘Idle’) mode is either Off, On or Hold Last

State.

Program to fault enable

When enabled, the outputs assume the fault value when a communication fault occurs while in

Program mode.

ReadBack

The state of each output point is reflected in the input tag.

Table 52 - 1715-IF16 Module Diagnostic Features

Feature

Description

Redundancy level

Simplex or duplex.

Redundancy status

The status of each module is available in the input tag.

Input range

Fixed as 0…20 mA.

Wiring

Single-ended only.

Data format

Read-only.

Scaling

Support choice of signal and engineering range.

Underrange overrange

Diagnostic alarms are provided when the signal goes above or below what the module is capable of

detecting. (Zero or less is considered underrange.)

Rolling timestamp

1 ms resolution.

Real time sample rate

Fixed RTS.

Table 53 - 1715-OF8I Module Diagnostic Features

Feature

Description

Redundancy level

Simplex or duplex.

Redundancy status

The status of each module is available in the input tag.

Input range

Fixed as 0…20 mA.

Scaling

Support choice of signal and engineering range.

ReadBack

The state of each output point is reflected in the input tag.