Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Appendix C

1715-IB16D Digital Input Module Diagnostics

For a full-diagnostics setting configuration, use these resistor values.

None Diagnostics Configuration

Selecting None in the Diagnostics pull-down menu loads a different set of default

values into the threshold settings. This is selected when no EOL devices are

used.

Figure 73 - None Diagnostics Threshold Default Values

Based on these settings, if the switch is closed, the input reports an ‘on’ condition

anytime the voltage is above ~14.5V, but does not report a short circuit, because

there is no way to get the voltage to rise to 32V.

The same is true with an ‘off ’ condition. The module reports an ‘off ’ condition

anytime the voltage is below ~5.5V, but does not report a wire off, because it has

to go below 0V to do so.

IMPORTANT

These are the most common commercially-available EOL devices.

Table 60 - Full Diagnostics Resistor Values

Item

Value

R1

15 k(1%) - power 0.5 W (max power dissipated 0.128 W)

R2

3.9 k(1%) - power 0.5 W (max power dissipated 0.128 W)

Loop supply voltage=

24V DC (±10%)

Indicates An

‘On’

Condition

Below 5.5V

Causes An ‘Off’

Condition