194

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 5

Configure the Redundant I/O System

The Configuration tab appears.

10. Click the Limits tab.

Table 37 - Analog Output Configuration Parameters Duplex Mode

Parameters

Description

Channel

Click the channel number to configure parameters for the specified channel (0…15).

Current Range

Displays the current range (0…20 mA) for the channel.
This field is read-only.

Low Signal

Check the Low Signal value for the channel (between 0.0…20.0 mA). The default is
4.0 mA. This value must be less than the High Signal value. Low Signal and Low Engineering values are shown in

pairs.

Low Engineering

Check the Low Engineering value for the channel (between -9999999…99999999). The default is 0.0. Low Signal

and Low Engineering values are shown in pairs.

High Signal

Check the High Signal value for the channel (between 0.0…20.0 mA). The default is 20.0 mA. This value must be

greater than the Low Signal value. High Signal and High Engineering values are shown in pairs.

High Engineering

Check the High Engineering value for the channel (between -9999999…99999999). The default is 100.0. High

Signal and High Engineering values are shown in pairs.

Hold for Initialization

Set the channel to hold, or not change, until initialized with a value within 0.1% of full scale of its current value

when one of these conditions occurs:

Module initial connection (powerup)

Module transition from Program mode back to Run mode

Module reestablishes communication after fault.