1715-IB16D Digital Input Module Diagnostics

Calculate Threshold and

Resistor Values

To arrive at the correct diagnostic settings, the user must know one of the two

values—either the threshold values or the resistor values, and then calculate the

other set of values from the known values.

The following example shows a typical EOL arrangement for an Emergency

Shutdown Device.

Figure 74 - Field Loop Circuit for Line Monitored Digital Input for Emergency Shutdown Systems

(ESD)

To better understand, the user must realize that by virtue of R1 and R2, in

combination with the module’s internal impedance and field switch position,

various voltage levels are produced at the input terminal that can be characterized

by the threshold values.

Knowing the resistor values allows you to calculate the voltage levels to arrive at

the threshold settings.

Use

Figure 75

and

Figure 76

, and the resistor values you choose. to determine

how the system responds to various field wiring conditions, so that the threshold

values can be set. For our example, we used the resistor values in

Table 60 on

page 274

.

Shield

(if used)

Terminal

Blocks

OV

20

Ω

100

Ω

50 mA

4.99k

Ω

Termination

Assembly

+24V dc

R1

R2

45678