Operating modes, Online mode, Offline mode – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 147: Shutdown mode

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

147

Using 1715 Analog I/O Module Features

Chapter 4

Operating Modes

This section discusses operating modes for the analog input and output modules.

Online Mode

When fully online and operational, each channel provides a regulated current

over a 1…24 mA range for the analog input module and a 0…24 mA range for the

analog output module. The current values are set for each channel by the

commanded values received from the running application. The module

indicators are GREEN, and with all module indicators GREEN, none of the

channels are in the failed state; however, the channel indicators depends on the

individual channel status.

In the online mode, you can add a module to a group (in a duplex TA), or change

a module in a pair, with no impact on the reported channel values or deviation

between the regulated current. The unaffected module of a pair provides the full

output values.

Offline Mode

The module is in the Offline mode when it is installed, but is not locked in

position (locking screw not engaged). All channel outputs are off and the channel

indicators are OFF. The Healthy indicator is GREEN and the Ready indicator

goes OFF, while the Run indicator is RED. The module enters the Shutdown

mode when locked in position.

When a critical power fault is detected, the module automatically enters the

Shutdown mode and the Healthy indicator goes RED before it goes into Ready

mode.

Shutdown Mode

In the Shutdown mode, all channels regulate their output to shutdown settings

for each channel. The Ready and Run indicators are RED.

In a group arrangement, one module can be in shutdown while the other can

continue to be online and in the Run mode and regulate the output according to

the commanded values.

When the module is communicating with the processors in Shutdown mode, it

transitions to the Ready mode. If there is an application running it transitions to

the Recover mode.

Advertising