Install the Adapter Base Unit

The adapter base unit supports a pair of adapter modules. The adapter base unit

has connections for two power feeds, four Ethernet ports, and two adapter

modules on the front of the unit, and a single I/O base connector on the right-

hand side of the unit. The connections for the adapter modules are commonly

referred to as adapter module slots.

To mount the 1715-A2A adapter base unit, follow these steps.

1. Place the 1715-A2A adapter base unit onto the DIN rails and position

them toward the left, leaving space for the I/O base units to the right.

2. Secure the adapter base unit onto the DIN rails by sliding the retaining

lever (below the base unit) to the left, as far as it goes, until it latches in the

locked position.

Install the I/O Base Unit

You can install up to three I/O modules on an I/O base unit. The I/O base unit

has an incoming I/O base connector on the left-hand side of the unit, an

outgoing I/O base connector on the right-hand side, and, on the front,

Adapter Base Unit

Retaining Lever

DIN Rails