1715 Redundant I/O System in SIL 2 Safety Applications

SIL 2 Safety Application

Requirements

To use the 1715 Redundant I/O system in SIL 2 safety applications, you must

have revision 2.001 or later, of the adapter firmware, the latest Add-on Profiles

and the 1715 SIL 2 Add-On Instructions.

1715 I/O Modules in SIL 2

Safety Applications

1715 I/O modules, firmware revision 2.001 and later

(1)

, can be used in safety

applications up to and including SIL 2. Your system can be configured with any

combination of I/O modules, and in either Simplex or Duplex mode.

Two new tabs have been added to the Module Properties dialog box to configure

modules for use in SIL 2 Safety applications:

The SIL 2 Safety tab lets you configure the RPI, connection reaction time

limit, access diagnostic data, and perform a SIL 2 reset, if necessary

The Input States When CRTL Expires tab lets you define the safe state for

inputs

For more information on SIL 2 application requirements for 1715 I/O modules,

see these resources:

Chapter 7,

starting on page

223

, for information about Add-On

Instructions for SIL 2 1715 I/O module applications

Appendix E,

starting on page

289

, for PFD and PFH calculations

Appendix F,

starting on page

303

, for a SIL 2 application checklist

IMPORTANT

For SIL 2 safety applications, you must have the following:
Firmware, revision 2.001 or later, for the 1715-AENTR adapter modules
Add-on Profile, version 2.01.014 or later, for the adapter and Add-on

Profile, version 3.01.014 or later, for the I/O modules

Add-On Instructions, version 2.001 or later, when using a ControlLogix

system

A 1756-L7 ControlLogix controller

ATTENTION: ControlLogix L7 controllers are certified in RSLogix 5000 version

20 or later for SIL 2 operations. See the latest certifications for software and
firmware at

http://www.rockwellautomation.com/rockwellautomation/

certification/overview.page

. See the TÜV website at

http://www.tuvasi.com

for

SIL 2 certification listings.

IMPORTANT

Listen Only is not supported for SIL 2 operations. Only one 1756-L7 Logix
controller can connect to any I/O module within the 1715 rack for SIL 2 safety

functions.

IMPORTANT

Safety functions that are being edited online will not be SIL 2 certified from the
start of the online edits to the completion of the validation of the changes.

(1) See the Module Revision Release List available from the Product Certifications link on