Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 2

Installation Instructions

Figure 16 - Fuse Tags

1715 I/O modules’ F2 and F4 fusing faults cannot be pinpointed. Any F2 or F4

blown fuse is indicated by all healthy I/O module status indicators showing solid

red.

The adapter tags indicate each individual I/O module tag, ModAFault and

ModBFault, as shown in

Figure 17

.

Figure 17 - Adapter Tags Indicate Faults

IMPORTANT

After any fuse replacement or power-related issue on PWR-1/PWR-2, the Reset

button on the 1715-AENTR must be pressed to clear the fault and reset the
status indicator back to solid green.