The table describes the two ways a module sends data to the owner-controller.

Set RPI

The Connection tab on the Module Properties dialog box lets you enter a

requested packet interval (RPI). The RPI guarantees the slowest rate at which

data is multicast to the owner-controller.

The module’s actual data transfer rate can be faster than the RPI setting. But, the

RPI provides a defined, maximum period of time when data is transferred to the

owner-controller.

Topic

Description

Requested packet interval

A user-defined rate at which the module updates the

information sent to its owner-controller. This is also

known as Cyclic Data Transfer.

Change of state

Configurable feature that, when enabled, instructs the

module to update its owner-controller with new data

whenever a specified input point transitions from On to

Off and Off to On. The data is sent at the RPI rate when

there is no change of state. By default, this setting is

always enabled for input modules.