148

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 4

Using 1715 Analog I/O Module Features

Ready Mode

All channels are off when in the Ready mode, the Ready indicator is GREEN and

the Run indicator is RED while the channel indicators are OFF. When an

application is started, the module transitions to the Run mode.

When a module loses communication with the processor, then it transitions back

to the Shutdown mode.

Run Mode

In the Run mode, all channels regulate the output current to the commanded

value for each individual channel. The Ready and Run indicators are GREEN.

You must make sure that all the user-required values have been set (by using

RSLogix 5000 or Logix Designer software) before transitioning the module to

Run mode.

If, for any reason, a module does not receive commanded values, then the module

transitions to the Shutdown mode.

Shutdown States

You can configure the channel shutdown states to do one of the following:

Turn-off/de-energize the channel
Hold last state
Regulate the output to a specified value

The shutdown state shall default to turn-off/de-energize.