Configure an output module add-on instruction – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 238

Advertising
background image

238

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 7

Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules

Configure an Output Module

Add-On Instruction

Follow these steps to configure an output module Add-On Instruction.

1. Add the Add-On Instruction to your routine from the Add-On tab of the

instruction toolbar.

2. Create a tag for the Add-On Instruction by using the default data type and

Read/Write External Access.
The tag can be controller- or program-scoped.

3. Create a reset tag by using the default data type and Read/Write External

Access.
The tag can be controller- or program-scoped.

4. Choose the module configuration tag.

If you have more than one module, be sure to choose the configuration tag

for the appropriate module.

5. Choose the module input tag.

If you have more than one module, be sure to choose the input tag for the

appropriate module.

6. Create a tag for the Reconciled Input Data by using the default data type

and Read/Write External Access.

Advertising