Chapter 7

Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules

8. Create a tag with the appropriate Add-On Instruction data type for the

Requested Output Data.

9. Enter the module RPI.

To optimize system bandwidth, type the same RPI value from the module

configuration.

Add-On Instruction Scan Times

Safety Reaction Time Calculations

The 1715 AOIs process data at a rate of the module RPI / 2. For example, if the

1715-IF16 RPI = 100ms, the 1715 IF16 AOI will process the most recent packet

every 50ms. This provides a compromise between controller bandwidth (not

processing the packets too often using old data) and overall 1715 screw to screw

performance. Because the 1715 AOIs run on a time basis, the input module AOI

and the output module AOI can be asynchronous. See

page 231

for additional

Table 47 - Maximum Scan Rates Measured

Module

Add-On Instruction

Scan Rate µs (max measured)

1715-AENTR

AENTR_SIL2

Duplex

455

1715-IB16D

IB16D_Simplex_SIL2

Simplex

340

1715-IB16D

IB16D_Duplex_SIL2

Duplex

378

1715-IF16

IF16_Simplex_SIL2

Simplex

831

1715-IF16

IF16_Duplex_SIL2

Duplex

832

1715-OB8DE

OB8DE_Simplex_SIL2

Simplex

501

1715-OB8DE

OB8DE_Duplex_SIL2

Duplex

541

1715-OF8

OF8I_Simplex_SIL2

Simplex

951

1715-OF8

OF8I_Duplex_SIL2

Duplex

964