Connect field wiring – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 79

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

79

Installation Instructions

Chapter 2

Connect Field Wiring

Connect the field wiring to the screw terminal blocks on the termination

assemblies.

IMPORTANT

The termination assemblies have integral fuses.

IMPORTANT

You must use safety wiring principles if the applicable standards for the system
require you take precautions to avoid external short circuits, because the

internal diagnostics in the 1715 adapter do not detect external short circuits
between channels. These standards include NFPA-72.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connections

to this equipment must be powered from a source compliant with safety extra
low voltage (SELV) or protected extra low voltage (PELV).

ATTENTION: To comply with UL restrictions, all connections to this equipment

must be powered from a UL. Listed source compliant with Limited Voltage/
Current per UL 508.