Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules

Chapter 7

information. The actual process rate is affected by the periodic task rate and

periodic task scan time.
The worst case safety reaction time can be calculated using the formulas shown

below.

For the example below, assume the following:

1715 Input Module RPI = 60 ms
1715 Output Module RPI = 80 ms
SIL 2 Task Period = 30 ms
SIL 2 Task Watchdog = 20 ms
AOI Module RPI=60 ms

If you are not using COS, the worst case reaction time from input screw terminal

to output screw terminal is equal to 210 ms plus the following:

Input RPI
Output RPI
Add-On Instruction Module RPI/2
SIL 2 Task Period x 6

SIL 2 Task Watchdog x 2

Table 48 - Worst Case Reaction Time Calculations

Worst Case Factors

Value

Fixed

Time (ms)

User

Configurable

Time (ms)

Description

1715 Input Module Delay

15

1715 Backplane Rate

65

1715-AENTR Delay

25

Input Data to ControlLogix

COS=NO

1715 Input Module RPI

60

COS = Change of State

COS=YES

Fixed

60

Add-On Instruction Module RPI

AOI Module RPI/2

30

Value entered into the AOI Module_RPI parameter

ControlLogix SIL2 Task Period

SIL 2 Task Period

30

Input data asynchronous to scan

ControlLogix SIL2 Task Period

SIL 2 Task Period

30

SIL 2 task period

ControlLogix SIL2 Task Period

SIL 2 Task Period

30

SIL 2 task period

ControlLogix SIL2 Task Watchdog

SIL 2 Task Watchdog

20

ControlLogix system runs input module AOI and controls requested

output
Assumes requested output in same SIL 2 task as 1715 SIL 2 AOIs

Add-On Instruction Module RPI

AOI Module RPI/2

30

Value entered into the AOI Module_RPI parameter

ControlLogix SIL2 Task Period

SIL 2 Task Period

30

AOIs are timer based; input and output AOI timers can be

asynchronous

ControlLogix SIL2 Task Period

SIL 2 Task Period

30

SIL 2 task period

ControlLogix SIL2 Task Period

SIL 2 Task Period

30

SIL 2 task period

ControlLogix SIL2 Task Watchdog

SIL 2 Task Watchdog

20

ControlLogix system runs output module Add-On Instruction and

places requested outputs in output module raw data

Output Data to 1715-AENTR

1715 Output Module RPI

80

1715-AENTR Delay

25

1715 Backplane Rate

65

1715 Output Module Delay

15