Status Indicators

Appendix A

Status indicators for the 1715-AENTR adapter module are shown in this table.

Table 54 Adapter Status Indicators

Indicator

State

Description

Module Status

Steady off

No power - There is no power to the module.

Steady green

Module operational - The module has been configured

without any faults.

Flashing green

Standby - The module has not been configured.

Steady red

Major fault - The module has detected a nonrecoverable

fault.

Flashing green/red

Self-test - The module is performing its power-on self

tests.

Flashing amber

Unlocked - Adapter is unlocked from a previously locked

state.

Redundancy Status

Steady off

No power, unlocked, or no partner - The module is not

locked (via the locking screw), or no partner module is

present.

Steady green

Synchronized - The module is synchronized with the

partner module (redundant operation).

Flashing green

Partner detected, synchronizing - The partner module has

been detected and is synchronizing with its partner

module in preparation for redundant operation.

Steady red

Synchronization fault - The partner module is present, but

unable to synchronize (no redundant operation).

Flashing green/red

Self-test - The module is performing its power-on self

tests.

Flashing amber

Unlocked - Adapter is unlocked from a previously locked

state.

Network Status

Steady off

No power, unlocked, no IP address - The module has no

power, or the module is not locked (via the locking screw),

or no IP address has been assigned or obtained.

Steady green

Connected - The module has at least one established

connection (either to itself or to an

I/O module).

Flashing green

No connections - The module has an IP address, but there

are no established connections (either to itself or an I/O

module).

Flashing red

Connection timeout - One or more of the connections

(either to itself or to an I/O module) has timed out.

Steady red

Duplicate IP - The module has detected that its IP address

is already in use.

Flashing green/red

Self-test - The module is performing its power-on self

tests.

Flashing amber

Unlocked - Adapter is unlocked from a previously locked

state.