I/o termination assemblies – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 46

Advertising
background image

46

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

Chapter 2

Installation Instructions

I/O Termination Assemblies

I/O termination assemblies are inserted into the I/O base units. There are eight

types of termination assemblies (two for each module) depending on the

architecture of your system and the I/O modules you are going to use.

Digital Input Termination Assemblies

Digital input termination assemblies support these features:

16-channel simplex TA provides termination for 16 digital input channels
Industry-standard field device connections at terminal blocks
24V DC digital input channels with a load of 5.11 k



per input channel

Individually fused channels with over voltage input protection

There are two types of digital input termination assemblies:

A 1715-TASIB16D, 16-channel simplex TA that provides termination for

16 digital input channels and mates with a single 1715-IB16D digital

input module

A 1715-TADIB16D, 16-channel duplex TA that provides termination for

16 digital input channels and mates with up to two 1715-IB16D digital

input modules

Table 6 - I/O Termination Assembly Descriptions

I/O Module

Termination Assembly Cat. No.

Termination Assembly Description

1715-IB16D

1715-TASIB16D

Digital input simplex

1715-TADIB16D

Digital input duplex

1715-OB8DE

1715-TAS0B8DE

Digital output simplex

1715-TADOB8DE

Digital output duplex

1715-IF16

1715-TASIF16

Analog input simplex

1715-TADIF16

Analog input duplex

1715-OF8I

1715-TASOF8

Analog output simplex

1715-TADOF8

Analog output duplex

Advertising