Install the power supply – Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 63

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

63

Installation Instructions

Chapter 2

Install the Power Supply

Power supplies must be installed to the left of the adapter base unit in a position

where the 24V DC supply wiring can be kept reasonably short.

Figure 25

shows

an example of a mounted power supply.

Figure 25 - Power Supply

The 1715 Redundant I/O System requires 24V DC power with a tolerance

between 18…32V DC. The system has been designed to operate with most

commercially available industrial uninterruptable power supplies (UPS). To

select a suitable power supply, calculate the overall system load that must be

powered (by using the table below), include any additional devices and add a

contingency allowance between 25…50%.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connections
to this equipment must be powered from a source compliant with the

following:

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV)

Power Supply

32070-M

Component

Power Requirement

Adapter module

8.0 W

Digital input module

4.0 W

Analog input module

4.0 W

Digital output module

3.0 W

Analog output module

3.6 W

Power supply

Varies