Calculate the Voltage for Off/On Conditions for Threshold Values

The following examples calculate the voltage for an ‘off ’ condition with the

switch opened and closed.

Open Switch/Off Condition

With SW1 open, current flows through R1 and R2 (15 + 3.9 k



18.9 k

. We

can calculate the voltage that is present at the input of the input module and by

using a voltage divider circuit, we can calculate the voltage for an ‘off ’ condition.

Figure 75 - Open Switch/Off Condition

Shield

(if used)

Terminal

Blocks

OV

20

Ω

100

Ω

50 mA

4.99k

Ω

Termination

Assembly

+24V dc

R1

R2

45678

User-calculated Voltage

5.1K

SW1

3.9k

15k

45680