Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

279

1715-IB16D Digital Input Module Diagnostics

Appendix C

Closed Switch/On Condition

If SW1 is closed, then current only flows through R2, so to calculate the voltage

present at the input module, use the R2 value of 3.9 kRtotal

Figure 76 - Closed Switch/On Condition

Shield

(if used)

Terminal

Blocks

OV

20

Ω

100

Ω

50 mA

4.99k

Ω

Termination

Assembly

+24V dc

R1

R2

45678

Solution For Voltage

5.1K 

SW1

3.9k

15k

Solution For Voltage

45681