Shutdown State

The output module shutdown state defines the behavior of the output module if

communications to the module fail within the timeout period or if the processor

is put into Program mode. This occurs on a channel-by-channel basis. These

principles apply for the 1715 analog and digital output modules.

The shutdown state can be configured to these values:

On-energize
Off-de-energize
Hold last state

During normal operation with an adapter present, the state of the outputs can be

configured when no connections from a Logix controller are active.

Analog output modules can be configured to OFF, HOLD LAST VALUE, or

GOTO SPECIFIED VALUE.

In Shutdown mode, the analog output module will TURN OFF all channel

status indicators irrespective of the value being output.

Energize-on-communication-failure

The 1715 Redundant I/O System can be a part of an energize-on communication

failure system. This means that during a system fault, the output module can be

set so that the output is energized. This is on a point-by-point basis. The

following are examples of energize-to-trip uses:

A fan that runs a ventilation system
Emergency lights