Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 237

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

237

Using SIL 2 Add-On Instructions with 1715 Redundant I/O Modules

Chapter 7

6. Create a tag for the Reconciled Input Data by using the default data type

and Read/Write External Access.
The tag can be controller- or program-scoped.

7. Enter the module RPI.

To optimize system bandwidth, type the same RPI value from the module

configuration dialog box.

Advertising