Rockwell Automation 1715-OF8I Redundant I/O System User Manual User Manual

Page 77

Advertising
background image

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014

77

Installation Instructions

Chapter 2

For each power supply connection, follow these steps.

1. Connect the negative line from the power supply, typically labelled ‘OV’,

to the left-hand terminal.

2. Connect the positive line from the power supply, typically labelled ‘+24V’,

to the right-hand terminal.

3. Apply a minimum tightening torque of 0.5 N•m (0.37 lb•ft) to the

terminal screws.

For maximum protection, be sure that the PWR-1 and PWR-2 plugs are supplied

from independent 24V DC sources as in

Figure 28

. Only having one power

supply plug connection causes a Rack Status fault status indicator to illuminate

on adapter modules.

Figure 28 - Independent Power Sources

Table 11 - Module Power Wiring Sizes

Wiring Attribute

Size

Conductor cross section, stranded maximum

2.5 mm

2

(12 AWG)

Conductor cross section, solid maximum

2.5 mm

2

(12 AWG)

Stripping length

7 mm (9/32 in.)

MP-PWR-24V1

OV

MP-PWR-24V2

OV

32125-M

PWR 1

PWR 2