Bandwidth @ -3dB = 50Hz ~ 20kHz.

Maximum Cable Length

100m on Category 5 cable

4.2.8 CD8

4.2.8.1 Overview

CD8 Wall mounted cabinet remote paging console for Ateis audio processor.

Wall-mount heavy duty remote paging console with Access level 2 protection to comply with the EN 54-

16. Compatible with Ateis audio processor and communicates over a dedicated RS485 for Power, audio

and DATA.

The unit comprises of 8 zones / 8 buttons with fist firemen’s microphone in a metal surface mount wall-

box. It provides robust IP-30 protection. Each CD8 contains a PMM PS Master PCB with extension

keypad and uses the same architecture as for the PPM AS series of microphone consoles. Each Ateis

audio processor like IDA8C can handle up to 31 CD8 units per 485 port in Master/Slave configuration.

(Note that only the Master unit is secured, Slaves are not).

The buttons can represent a single zone or a group of zones. All buttons can be programmed with drag

& drop features from the software, The PTT button can be programmed for Push To Talk or for latching

functionality.

The unit offers “Hold” and “Busy” LED signals in addition to the zone LED’s, and these allow the easy

identification of Selection / Busy signals for the user. In addition, to comply with EN 54-16, separate

POWER, FAULT and EVAC indicators are provided.

The RS485 communication protocol offers daisy chaining of up to 300 m on a simple CAT5 cable, and