Leakage occurrence:

If leakage impedance lower than the leakage threshold which is defined in [Global Settings] tab, then

a Leakage Occurrence fault is recognized.

If the internal values of monitoring Line A/B become not normal, IDA8C/S will detect and recognize

that error, then generate a global fault Line A/B Error, the error status is showed in the field

[Measure(ohm)]. There are three kinds of Line A/B Error listed below:

Line A/B Open

If the value of Measure (ohm) is greater than 4000 ohm, this fault can be recognized by IDA8C/

S, In the field of [Measure(ohm)] shows "OPEN".

Line A/B Bad Impedance

If the value of Measure (ohm) is greater than Reference A&B (ohm) + Tolerance (%), or value of

Measure (ohm) is less than Reference A&B (ohm) - Tolerance (%), this fault can be recognized

by IDA8C/S. In the field of [Diff(%)] shows the percentage of difference, in above figure, the

difference percentage of zone 4 is 78.24 which is great than the tolerance 15%, a Line A/B bad

impedance is recognized.

Line A/B Short

The voltage of pin +, - is monitored by IDA8C/S, if the voltage is zero, it means there is a short

of circuit outside IDA8C/S, if this fault is detected, the internal relay of zone will be open to stop

audio signal output to speaker. User need to do a Reset Monitoring described in preview part of

this topic to switch the status back, i.e. make audio output to speaker and enable monitoring of

short again. A string "S.C." is showed in field [Measure(ohm)]