App preset value, Watchdog timer – Yokogawa Touch Screen GP20 User Manual

Page 131

Advertising
background image

1-117

IM 04L51B01-01EN

Configuring the GX/GP

1

2

3

4

5

App

Preset value

1

Setup Item

Selectable Range or Options

Default Value

Preset value

–9.999999E+29 to 9.999999E+29

–9.9999999E+29 to –1.0000000E–30, 0,

1.0000000E-30 to 9.9999999E+29

0

1 Appears when On/Off is set to

On.

Preset value

Set the preset value.

Watchdog timer

Setup Item

Selectable Range or Options

Default Value

On/Off

Off, On

Off

Timer

1

1 to 120 (s)

30

Value at timer-expired

1

Last value, Preset value

Last value

1 Appears when the watchdog timer is set to

On.

On/Off

Set this to

On to use the watchdog timer.

Timer

Set the duration for monitoring values that fail to be updated.

If a value is not updated within the specified duration, the value is replaced.

Value at timer-expired

Set whether to set the value when the timer expires to the last value or preset value.

Explanation

Watchdog Timer Function

Data may fail to be updated due to Modbus or other communication problems. The

watchdog timer function replaces values with preset values or last values at power-on and

when values are not updated within the specified duration (timer).

Data replacement occurs immediately at power-on and the timer expires, and the values are

held until the next communication interval.

Timer

Power on

Data not updated

Communication

channel data

Replace data

A

B

C

D

E

E

E

Preset value: Z

Z

Z

F

G

Read cycle

Replace data

Communication data

H

1.15 Configuring Communication Channels (/MC option)